Are the circuit breaker bus plugs, used on riser busway, different than the standard plug in units?
Issue:
Are the circuit breaker bus plugs, used on riser busway, different than the standard plug in units?
Product Line:
Busway
Environment:
Application
Cause:
Clarification/Selection
Resolution:
The 800 amp and above Busplugs (Those with catalog numbers beginning with PTQ) need to be specified ("H" for horizontally mounted ) , or ("V" for vertically mounted).. The smaller amperage units (600A and below, beginning with PT) are the same as those used on horizontal runs.
CTA-ID : 2005901
Are the circuit breaker bus plugs, used on riser busway, different than the standard plug in units?
Product Line:
Busway
Environment:
Application
Cause:
Clarification/Selection
Resolution:
The 800 amp and above Busplugs (Those with catalog numbers beginning with PTQ) need to be specified ("H" for horizontally mounted ) , or ("V" for vertically mounted).. The smaller amperage units (600A and below, beginning with PT) are the same as those used on horizontal runs.
CTA-ID : 2005901