What does the 24 Vdc power supply do when provided on an ammeter trip unit for P-frame, R-frame, and Masterpact breakers?

Issue:
What does the 24 Vdc power supply do when provided on an Ammeter trip unit for P-frame, R-frame, and Masterpact breakers?

Product Line:
Powerpact P-frame, Powerpact R-frame, Masterpact

Resolution:
Without the 24V DC power supply the Ammeter trip unit:
  • Provides fault protection for LSIG functions
  • Provides LED trip indication (powered by an onboard battery)
  • Ammeter and bar graph powers with the current flow on one phase of 25% or more of the sensor rating.
  • Ground fault push-to-trip button works for testing ground fault with current flow on one phase of 25% of the sensor rating or more.

With the 24V DC power supply wired to F1 (- terminal) and F2 (+ terminal) on the terminal block on top the the trip unit, the Ammeter trip unit:
  • Provides all of the above
  • Ammeter and bar graph displays are functional below 20% of the sensor rating current flow on one phase
  • Ground fault push-to-trip button works for testing ground fault with no current flowing through the breaker
  • Highest fault current reading and phase that tripped
  • Optional Modbus communications

Ground fault push-to-trip button will also be functional if a hand held test kit or full function test kit is powering the trip unit.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings