Can the larger Homeline branch breakers (HOM2150BB, HOM2175BB, HOM2200BB, and subfeed lug kit HOML2225) be used in any Homeline load center?
Issue:
Homeline large branch circuit breakers

Product Line:
Homeline Load Centers

Resolution:
No, these branch breakers and the subfeed lug kit can ONLY be applied in a Square D Homeline convertible mains  load center, Series S01, S02, S03 or S04, rated 150 A or higher. The branch breaker ampacity cannot exceed the load center mains ampacity rating.