Is there a 5% limit for the single phase loading on Delta-Delta connected Transformers with 240/120 Center Tapped secondaries?


Issue:
Center tap capacity of a center tapped delta secondary

Product Line:
LV Transformers

Environment:
Applies to Transformers with center tapped delta secondaries by SquareD/Schneider Electric

Cause:
Center tap capacity must be limited based on Transformer design factors

Resolution:

Delta-Delta connected Transformers are intended to supply balanced three-phase loads, such as motors and compressors. Unbalanced loading can cause a circulating current to flow in the windings. This additional current is like a ``hidden`` load with the Transformer windings and can severely de-rate or even overload the Transformer. Adding a Center Tap on the secondary for a combination of a 240V three-phase and 120V single-phase loads can exacerbate the effect in a more severe imbalance.  When applying 240/120V Secondary Three Phase Transformers by SquareD/Schneider Electric, such as those with catalog numbers ending in T6HCT, the amount of the imbalance allowed when using the Center Tap (CT) to feed 120V loads is limited to 5% of the overall rated KVA of the Transformer to help prevent excessive circulating currents.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings