What does suffix 2100 indicate on a legacy circuit breaker?

Issue:
What is suffix 2100 and how does it work?

Product Line:
All products with this suffix.

Resolution:
Suffix 2100 indicates a normally open bell alarm contact.
A bell alarm changes state only if the breaker trips or is reset. The 2100 is normally open and closes when the breaker trips.