What is the difference between a shunt trip and shunt close device on a Masterpact breaker?

Issue:
What is the difference between a shunt trip and shunt close module on a Masterpact NW or NT breaker?

Product Line:
Power circuit breakers

Resolution:
There is no difference in the accessory and they are marked to be used as either. Their function is determined by which position they occupy in the breaker. When used as a shunt trip, the coil trips the breaker when the rated voltage (Vn) is applied. When used as a shunt close, the coil closes the breaker when Vn is applied as long as there is nothing preventing the breaker from closing (an open command, the open button being pressed, and engaged padlock attachment, etc.) See attached instruction bulletin 48049-146-01 for more information.

Schneider Electric Canada

Attachment(s)
MX MN 48049-146-01.pdf [161.17 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings