Video: How do you wire a QO/QOB shunt trip breaker (ex. QO120-1021)?

Product Line:
Circuit Breakers
QO

Environment:
Electrical Distribution Equipment

Resolution:
Connect the appropriate voltage (ie. 120V to 240V for the -1021 suffix) to the two terminals on the shunt trip. Land the switch leg from the source contact on one terminal (either) and the neutral wire (L2 , X2 ) to the other terminal. The shunt trip has coil clearing contacts that open when the voltage is applied so either momentary or maintained contacts can be used to initiate voltage.
Shunt trip accessories in QO(B) are factory installed only and can not be added to an existing breaker.
The accessory terminals will accept (2) #14 - 12 Al/Cu.



Sample wiring diagram

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings