What are the recommendations regarding conduit sizing and type of wire for the installation of a Hospital Isolated Power System?

Issue:
Recommendations regarding conduit sizing and type of wire for the installation of a Hospital Isolated Power System.

Product Line:
Medical Products

Environment:
Installation

Cause:
Recommendation

Resolution:
Square D recommends a minimum conduit diameter of 3/4``, one circuit per conduit, a maximum of 360 degrees of bend per conduit run, and absolutely no pulling compound of any type. The recommended wire is XHHW-2. Additional references are NFPA 99 and NEC Article 517.


Schneider Electric Canada

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings