Issue:
What is the lug size and wire bending wire capacity for the Main lugs of a HCP5086-12N I Line Panelboard interior?
Product Line:
I Line Panelboards
Environment:
Termination Features
Resolution:
The lug will accommodate up to (4) 3/0 to 750 kcmil Al/Cu wire per phase, but due to NEC wire bending space, only up to (4) 3/0 to 500 kcmil Al/Cu wire, per phase, may be terminated to the Main lugs.