Is there a reason for unusual voltages measured to ground when connecting Buck and Boost transformers according to single phase diagram #4?

Issue:
Stray voltages to neutral or ground from a Buck and Boost Transformer connection
Product Line:
Low Voltage (LV) Transformers
Environment:
Applies to Buck Boost Transformers by SquareD/Schneider Electric
Cause:
Magnetic voltages from an ungrounded single phase Buck Boost Transformer connection
Resolution:
Wiring diagram #4 indicates a single phase buck or boost scenario in which there is usually no ground reference. Unusual voltage readings from the circuit to ground are not indicative of a problem and may be ignored.  The important voltages are found between the LV and HV inputs or outputs of the diagram.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings