Issue:
Type 1 & Type 2 short circuit coordination comparison
Product Line:
Starters and Contactors
Environment:
Products sold in North America
Resolution:
Type I - Under short circuit conditions, the contactor or starter shall cause no danger to persons or installation and may not be suitable for further service without repair and replacement parts.
Type II - Under short circuit conditions, the contactor or starter shall cause no danger to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manufacturer shall indicate the measures to be taken in regards to equipment maintenance.
For additional information on Understanding Type 2 Coordination please refer to Link below in document # 0140PD9202.
https://www.se.com/us/en/download/document/0140PD9202/
Type 1 & Type 2 short circuit coordination comparison
Product Line:
Starters and Contactors
Environment:
Products sold in North America
Resolution:
Type I - Under short circuit conditions, the contactor or starter shall cause no danger to persons or installation and may not be suitable for further service without repair and replacement parts.
Type II - Under short circuit conditions, the contactor or starter shall cause no danger to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manufacturer shall indicate the measures to be taken in regards to equipment maintenance.
For additional information on Understanding Type 2 Coordination please refer to Link below in document # 0140PD9202.
https://www.se.com/us/en/download/document/0140PD9202/
Released for: Schneider Electric Canada
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.