Can a 3-pole breaker be used in a 2-pole application?
Issue:
Three pole breaker use in two pole (single-phase) application
Product Line:
MCCB
Environment:
Powerpact and Masterpact
Resolution:
Powerpact M P and R
Three pole breaker use in two pole (single-phase) application
Product Line:
MCCB
Environment:
Powerpact and Masterpact
Resolution:
- A 3p breaker can be used on a 3 phase system using either 2 or 3 poles.
- A 3p breaker can be used on a 1 phase system only if indicated by the markings as noted below.
- Per NEC article 240.85: "A circuit breaker with a straight voltage rating, such as 240V or 480V, shall be permitted to be applied in a circuit in which the nominal voltage between any two conductors does not exceed the circuit breaker’s voltage rating."
- According to UL's White book, "3–pole circuit breakers are suitable for use on 3-phase systems only, unless marked to indicate use on 1-phase systems, such as, “For 1–phase connections, use two outside poles,” or an equivalent statement. A 3-pole breaker used in place of a 2-pole breaker on a 3-phase system, such as a 2-pole breaker used in a branch circuit that is actually two legs of a 3-phase system, is acceptable without the 3-pole breaker being specifically marked."
Powerpact M P and R
- Three-pole M, P, and R frame breakers have a marking on the cover that states "single phase any 2 poles."
- Three-pole Powerpact L frame Micrologic breakers with all trip units (U31X, U33X, U43X, U44X, U53X and U54X) are marked for single-phase use, but on 240Vac circuits only. Use any 2 poles.
- Three-pole Powerpact H and J-frame thermal-magnetic breakers are marked for single phase use, including MCP.
- Three-pole Powerpact H and J-frame Micrologic breakers with standard trip units (U31X and U33X) are marked for single-phase use
- Three-pole Powerpact B frame breakers are not marked for single phase use.
- Three-pole Powerpact QB, QD, QG, QJ breakers are not marked for single phase use.
- Three-pole EDB, EGB, and EJB breakers are not marked for single phase use.
- Three-pole LA and LH type breakers are marked for single phase use. Use any two poles.
- Some three-pole legacy breakers are marked for single-phase use but most are not. Check the label for marking.
Released for: Schneider Electric Canada
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.