Issue:
Restrictions in an NF panelboard that limits mounting 125A branch breakers adjacent to each other on the bus
Product Line:
NF panelboards
Environment:
Installation
Resolution:
A 125A EDB breaker can have only a 20A maximum breaker mounted across from it due to the 145A maximum rating of the branch connector.