How can the Altivar ATV58 unit be set back to factory defaults?
Issue:
ATV58 factory defaults

Product Line:
Altivar 58, ATV58

Environment:
All

Cause:
ATV58 factory parameters defaults

Resolution:
NOTE: Please refer to the documentation associated with the product for further information cautions or warnings that may apply to this issue.

Factory settings may or may not match the application and control wiring. Please verify proper settings.
For best results, remove the connections to the control terminal strip on the main control board.
The drive shall not be in serial link control.

Go to menu 7 (Files FLS).
Enter. Scroll down to FOt (Operation Type)
Enter. Scroll down to INI (Fact. Default)
Enter. The display will ask ``Wiring OK?``
Make sure there are no inputs active.
Enter. The display will ask ``Fact.Set?``
Enter. This will set the drive to factory default settings.