Can a single pole QO breaker be connected to the B phase of a three phase QO load center?

Issue:
Single pole Branch breaker use

Product Line:
QO Load centers and branch breakers

Cause:
Application

Resolution:
It will depend on the voltage system the load center is being applied on. On a 208Y/120Vac, 3Ph/4W system, you can connect a 120V single pole QO breaker to any phase. On a 240Vac Delta, 3Ph/4W system (aka: high leg, red leg or stinger leg), you could NOT use the single pole breaker on the high voltage phase (it would provide 208V to ground), but you could use a single pole breaker on the two phases providing 120V to ground. On a 240Vac Delta, 3Ph/3W system, you could NOT use the single pole breaker on any phase.


CTA-ID : 2017875

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings