Are Powerpact circuit breakers "kiss free" when the shunt trip is energized?
Issue:
Are the Powerpact breakers kiss free when the shunt trip is activated?
Product Line:
Powerpact Circuit breakers
Resolution:
The Powerpact H, J, L, M, P, and R frame breakers are "kiss free" when the shunt trip is energized. This means that the main contacts will not close, even for an instant, if a close attempt is made.
Are the Powerpact breakers kiss free when the shunt trip is activated?
Product Line:
Powerpact Circuit breakers
Resolution:
The Powerpact H, J, L, M, P, and R frame breakers are "kiss free" when the shunt trip is energized. This means that the main contacts will not close, even for an instant, if a close attempt is made.