Issue:
Application
Product Line:
QO and Homeline Load Center
Environment:
Application
Cause:
Clarification
Resolution:
No, branch neutral wires should only be terminated on the load center's neutral bar terminals, regardless if the panel is used as service equipment or a subpanel.