Can a GFI breaker be tested by creating a leakage to ground?
Issue:
Can we force a ground fault in order to ensure a GFI is working correctly?

Product Line:
Miniature Circuit Breakers

Resolution:
Yes, but this is not recommended. If the GFI is properly installed and functioning, the integral test button will trip the breaker. The test button creates a real ground fault through an 18000 ohm resistor. This is the only UL approved testing method.

Schneider Electric Canada

Can a GFI breaker be tested by creating a leakage to ground?
Issue:
Can we force a ground fault in order to ensure a GFI is working correctly?

Product Line:
Miniature Circuit Breakers

Resolution:
Yes, but this is not recommended. If the GFI is properly installed and functioning, the integral test button will trip the breaker. The test button creates a real ground fault through an 18000 ohm resistor. This is the only UL approved testing method.

Schneider Electric Canada

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.