Issue:
What is the terminal wire size and torque required for the STANDARD branch neutral bars in all load centers?
Product Line:
QO and Homeline Load Centers
Resolution:
The standard terminal sizes for the branch neutral bars in all the Homeline and QO load centers are shown below.
1) Homeline load center branch neutral bar terminal:
2) QO load center branch neutral bar terminals:
What is the terminal wire size and torque required for the STANDARD branch neutral bars in all load centers?
Product Line:
QO and Homeline Load Centers
Resolution:
The standard terminal sizes for the branch neutral bars in all the Homeline and QO load centers are shown below.
1) Homeline load center branch neutral bar terminal:
| Wire Range | TORQUE LB-IN |
| #4 CU/AL | 35 |
| #6 CU/AL | 35 |
| #8 CU/AL | 25 |
| #10 - #14 CU | 20 |
| #10 - #12 AL | 20 |
2) QO load center branch neutral bar terminals:
| TORQUE LB-IN | ||
| Wire Range (AWG) | Bar With 2 Screw Sizes Large Small | Bar With 1 Screw Size |
| 1/0 - 3 CU/AL | 50 ... | ... |
| 4 CU/AL | 45 ... | 35 |
| 6 CU/AL | 45 25 | 35 |
| 8 CU/AL | 40 10 | 25 |
| 10 - 14 CU, 10 - 12 AL | 35 10 | 20 |