What is the terminal wire size and torque required for the STANDARD branch neutral bars in all Homeline and QO load centers?

Issue:
What is the terminal wire size and torque required for the STANDARD branch neutral bars in all load centers?

Product Line:
QO and Homeline Load Centers

Resolution:
The standard terminal sizes for the branch neutral bars in all the Homeline and QO load centers are shown below.

1) Homeline load center branch neutral bar terminal:
Wire Range TORQUE LB-IN
#4 CU/AL35
#6 CU/AL35
#8 CU/AL25
#10 - #14 CU20
#10 - #12 AL20

2) QO load center branch neutral bar terminals:
TORQUE LB-IN
Wire Range (AWG)Bar With 2 Screw Sizes
Large            Small
Bar With 1
Screw Size
1/0 - 3 CU/AL50              ... ...
4 CU/AL 45               ... 35
6 CU/AL45                 2535
8 CU/AL40                 1025
10 - 14 CU, 10 - 12 AL 35                10 20