Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can the secondary main breaker in an MPZ10S40F be a GFI breaker?
Issue:
Can the secondary main breaker be  a GFI breaker in a sealed mini power zone unit substation?

Product Line:
Low Voltage Transformers

Environment:
Mini Power-Zone LV Substation

Resolution:
The standard secondary main breaker is a QO260. If a QO260GFI were used, the secondary would no longer have a neutral connection and would be limited to 240 volts only and no single-pole 120V branch breakers would be allowed.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings