How is the 80110-320-02 main breaker (NQMB2Q) , or subfeed breaker (NQSFB2Q) closing plate secured to the deadfront?
Issue:
The deadfront does not have mounting holes.
Product Line:
NQ Panelboard
Environment:
Installation
Cause:
Clarification
Resolution:
The closing plate is positioned behind the deadfront and the screws inserted from the front at the knockout 4 corners. The screw heads will catch the deadfront and draw the closing plate up tight to the deadfront.