Can I disable the ground fault section on an SE type micrologic GFI breaker, catalog number SEF362500LIG?

Ground fault can be disabled temporarily for test purposes only. The next best thing is to either replace the trip unit with one with suffix LSIA, or turn the pickup and delay switches to maximum.