{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
What is the difference between instantaneous, trip indicating and electrical fault indicating auxiliary contacts on the GV7 starters?
Product Line:

Tesys GV Manual Starter and Protectors

Resolution:
Instantaneous contacts change status with the opening and closing of the (power contacts) starter poles.

Trip indication contacts change state when the starter has tripped due to an overload, short-circuit, differential fault or phase imbalance, operation of undervoltage trip module, shunt trip, or by initiating the `push to trip`` button. The contact resets when the starter is reset.

Electrical fault indication contacts change state when the starter has tripped due to an overload, short-circuit, differential fault or phase imbalance. The contact resets when the starter is reset.

Schneider Electric Canada

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: