How can we help you today?

Is it possible to use one variable speed drive to run multiple motors at one time?


Resolution:

Yes. A single Variable Speed Drive (VSD) can operate multiple motors simultaneously, provided that all motors are intended to run at the same speed and frequency. Since the drive supplies a common output frequency, independent speed control of individual motors is not possible.

Conditions

The following conditions must be met when using one drive to control multiple motors:

  • All motors must start and run at the same time.
  • All motors will operate at the same output frequency commanded by the drive.
  • The combined motor load must not exceed the drive's rated capacity.
  • The application must not require individual motor speed regulation.
  • Each motor will need to have its own motor thermal protection device.

Drive Sizing and Configuration

When selecting and programming the drive:

  • Set the Nominal Motor Current parameter to the sum of the Full Load Amps (FLA) of all connected motors.
  • Set the Rated Motor Power parameter to the total horsepower (HP) or kilowatt (kW) rating of all connected motors.
  • Verify that the sum of all motor currents does not exceed the drive's rated output current.
  • Verify that the total motor power does not exceed the drive's rated power.

Protection Requirements

The drive's internal motor overload protection is designed for a single motor and does not adequately protect multiple motors connected in parallel.

Therefore:

  • Each motor must have its own overload and/or over-temperature protection device.
  • Individual motor protection must comply  with Article 430, Part C of the National Electrical Code, and any applicable local electrical
    codes.
  • An overload event on one motor must either:
    • Command the drive to stop, or
    • Disconnect the affected motor from the drive output

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)




Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings