Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Can Masterpact or Powerpact circuit breakers with Micrologic trip units be used on 400 Hz electrical systems?
Product Line:
Masterpact and Powerpact Circuit breakers

Environment:
Products used in the US

Resolution:
Masterpact breakers and Powerpact M, P, and R frame breakers cannot be used on 400Hz systems.

Powerpact H, J, and L-frame breakers can be used on 400Hz systems, but need to be derated. See the catalog
for H, J, and L-frame derating information. (Note: Not UL Listed)