Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Are the Class 8536 Type S starters suitable for use for group motor applications?
Issue:
Can the Class 8536 Type S starters be used on group motor applications?

Product Line:
Nema and Definite Purpose and Starters

Environment:
Type S Contactors and Starters

Cause:
Needs the know if the Class 8536 Type S starters suitable for use for group motor applications.

Resolution:
No, these NEMA rated devices provide no short circuit protection and therefore are not suitable for use for group motor.