Can a QO, 2 pole GFI breaker be used for a combination of 240 Vac and 120 Vac loads?
Issue:
Is it possible to use the QO 2 pole GFI in a 120Vac and 240Vac system?

Product Line:
Miniature Molded Case Circuit Breakers

Resolution:
Yes, as long as the neutral for the 120 Vac loads is connected to the neutral terminal on the breaker and the pigtail is connected to the neutral bar in the panel.

EXCEPTION: The QO260GFI does not have a load neutral connection, and is therefore not viable for this application.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and en expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Center

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings