Can the LR2D or LRD overload relay with single phase sensitivity and a D-Line contactor be used on single phase applications?

Issue:
Need to use a three phase overload relay in single phase application.

Product Line:
Tesys D line overload relays

Environment:
Products sold and used in the United States

Cause:
Using a single phase sensitive overload in a single phase application

Resolution:
Yes, it is possible to use the OLR`s with single phase sensitivity on single phase motors if wired correctly. The recommended connection is to bring line side connections to terminals L1 & L3 on the contactor, jumper T1 on the overload to L2 on the contactor, and run load side connections off T2 and T3 of the overload. You must ensure current passes through all three phases or else the OLR will trip on a phase imbalance.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings