Issue:
Adjustable trip ranges for MCP
Product Line:
Molded Case Circuit Breakers
Resolution:
The following table shows the adjustable trip range of the H-frame motor circuit protectors:
Adjustable trip ranges for MCP
Product Line:
Molded Case Circuit Breakers
Resolution:
The following table shows the adjustable trip range of the H-frame motor circuit protectors:
Catalog Number | Sensor Rating | Full Load Amperes | Adjustable Instantaneous Trip Range | ||
---|---|---|---|---|---|
HJL36030M71 | HLL36030M71 | HRL36030M71 | 30 A | 1.5-25 A | 9-325 A |
HJL36050M72 | HLL36050M72 | HRL36050M72 | 50 A | 14-42 A | 84-546 A |
HJL36100M73 | HLL36100M73 | HRL36100M73 | 100 A | 30-80 A | 180-1040 A |
HJL36150M74 | HLL36150M74 | HRL36150M74 | 150 A | 58-130 A | 348-1690 A |