Does SquareD/Schneider Electric make a 3 phase Transformer with a neutral on the primary input side?
Issue:
Most three phase Transformers have Delta primaries, with no neutral
Product Line:
LV Transformers
Environment:
Applies to LV Transformers by SquareD/Schneider Electric
Cause:
Delta Primaries are inherently more stable
Resolution:
SquareD/Schneider Electric provides Wye primary on Delta secondary with center tap Transformers (T151 voltage code). The primary of this unit does not provide a terminal for a neutral. Connecting the primary of a Transformer to the neutral point of a Wye system can cause troublesome neutral currents during times of imbalance. Generally, it is best to select a Delta primary for most 3 phase applications, even when connecting to a Wye power system. Other custom Wye primary Transformers may also be available for Solar and Alternative Energy applications. Inquire about these with your local SquareD/Schneider Electric Distributors and Field Offices.
Released for: Schneider Electric Canada




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.