What torque is needed for the wire binding screws for NFALM4 main lugs of a 400A NF panel?
Issue:
Torque Values for NFALM4 main lugs of a 400 NF Panel

Product Line:
NF Panelboard

Environment:
Maintenance

Cause:
Installation

Resolution:
Main lugs, and neutral wire binding screws should be torqued between 275-300 in lbs.