Can a breaker such as a JDP36200 be replaced by a JDL36200?
Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment.  Also pertains to JGL JGP, JDP JDL  JJL JJP JLL JLP JRL JRP

Resolution:
The lugs on the on end of the JDL breaker can be removed, and a terminal nut insert S37445, (a kit of 3) can be installed to complete the conversion.