How can we help you today?

What is the line dip ride through time for the ATV61 and ATV71 drives?

Issue:
What is the line dip ride through time for the ATV61 and ATV71 drives?

Product Line:
Altivar 61 and Altivar 71

Environment:
All

Cause:
Need to know how long the drive will 'ride through' a dip in line power

Resolution:

Maximum running time (without fault) at Under Voltage with Nominal Torque is:

1. 1000 msec. with a voltage 70% of nominal voltage
2. 500msec. with a voltage 40% of nominal voltage

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings