Are 65,000 or 25,000 AIC 120/240V rated breakers required on the secondary of this MPZB - 25K or 65K mini power zones?
Issue:
When selecting branch breakers for the mini powerzone MPZB devices, Do you select the 25K or 65K AIC rated breakers?
Product Line:
Mini Powerzone
Environment:
MPZ MPZB
Resolution:
No. The 25K or 65K AIC is for the main breaker only. The secondary branch breakers can be the standard 10,000 AIC breakers.