Are the NEMA combination starters supposed to have a ground strap from the door to the enclosure?

Issue:
Do UL508 require the NEMA combination starters to have a ground strap from the door to the enclosures?

Product Line:
NEMA and Definite Purpose Contactors and Starters

Environment:
NEMA Combination Starters

Cause:
Product Specifications

Resolution:
UL508 does not require a grounding strap from door to enclosure.  As such Schneider Electric does not supply a ground strap from the door to the box, but the hinges and hinge pins do provide a grounding connection.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings