Issue:
Do UL508 require the NEMA combination starters to have a ground strap from the door to the enclosures?
Product Line:
NEMA and Definite Purpose Contactors and Starters
Environment:
NEMA Combination Starters
Cause:
Product Specifications
Resolution:
UL508 does not require a grounding strap from door to enclosure. As such Schneider Electric does not supply a ground strap from the door to the box, but the hinges and hinge pins do provide a grounding connection.