{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Are the M800 circuit breaker enclosures suitable for use as service entrance equipment?

Article available in these languages: Spanish

Issue:
Application

Product Line:
Circuit Breaker Enclosure

Resolution:
Yes, these circuit breaker enclosures are marked "Suitable for use as Service Equipment".

Schneider Electric Canada

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: