Product Line:
Circuit Breakers
Resolution:
To meet requirements of higher ambient conditions, circuit breakers can be factory calibrated for a 50°C ambient temperature by using the CA Suffix. Circuit breakers with special thermal calibration such as CA suffix are not UL Listed. The CA suffix applies to Powerpact H, J, and Q thermal magnetic circuit breaker only.
NOTE: Electronic Powerpact breakers and Powerpact B beakers are not available with 50° calibration, however they can be applied in 50° C applications when derated properly. For more information on the electronic Powerpact H, J, L, M, P, and R frame breakers, see attached catalog pages with ambient derating tables.
Circuit Breakers
Resolution:
To meet requirements of higher ambient conditions, circuit breakers can be factory calibrated for a 50°C ambient temperature by using the CA Suffix. Circuit breakers with special thermal calibration such as CA suffix are not UL Listed. The CA suffix applies to Powerpact H, J, and Q thermal magnetic circuit breaker only.
NOTE: Electronic Powerpact breakers and Powerpact B beakers are not available with 50° calibration, however they can be applied in 50° C applications when derated properly. For more information on the electronic Powerpact H, J, L, M, P, and R frame breakers, see attached catalog pages with ambient derating tables.
Released for: Schneider Electric Canada




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.