Can two different gauge wires be placed under the same lug of a safety switch that allows for more than one conductor on the lug?

Issue:
Can two different conductor sizes be used on the same lug for safety switches?

Product Line:
Safety Switch

Environment:
Lugs of Safety Switch

Resolution:
No. The lug ratings do not allow for different gauge wires under same lug. All multiple conductors under a lug must be the same size.