| Voltage Code | Resistance (Ohms) | Inductance | DC Coil Voltage |
| AD | 4.41 | 0.18 | 5 |
| AL | 9.51 | 0.37 | 5 |
| BD | 101.9 | 3.9 | 24 |
| BL | 213.7 | 8.2 | 24 |
| CD | 207.7 | 8.1 | 36 |
| CL | 494.8 | 19 | 36 |
| DD | 1527 | 55 | 96 |
| DL | 3255 | 122 | 96 |
| ED | 392.7 | 15 | 48 |
| EL | 843.6 | 33 | 48 |
| FD | 2085 | 78 | 110 |
| FL | 4584 | 163 | 110 |
| GD | 2539 | 94 | 125 |
| JD | 26 | 1 | 12 |
| JL | 53.4 | 2.1 | 12 |
| KD | 1661 | 62 | 100 |
| LD | 6262 | 207 | 200 |
| MD | 7472 | 268 | 220 |
| ML | 17824 | 604 | 220 |
| ND | 633.3 | 24 | 60 |
| PD | 3923 | 143 | 155 |
| QD | 4845 | 177 | 174 |
| RD | 29692 | 923 | 440 |
| SCD | 50973 | 1653 | 575 |
| SD | 819.9 | 31 | 72 |
| SL | 1953 | 71 | 72 |
| TD | 14986 | 526 | 305 |
| UD | 9580 | 345 | 250 |
| UL | 22158 | 745 | 250 |
| VD | 18944 | 659 | 348 |
| XD | 59146 | 2053 | 600 |
| ZD | 66.4 | 2.6 | 20 |
| ZL | 147.6 | 5.5 | 20 |
Released for: Schneider Electric Canada


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.