Issue:
Need to know resistance or ohms value for the TeSys DC Coils on an LC1D09 thru LC1D38
Product Line:
Contactors and Starters IEC
Environment:
North American Products
Resolution:
Please see the table below for these values (within approximately + or - 10%)
Need to know resistance or ohms value for the TeSys DC Coils on an LC1D09 thru LC1D38
Product Line:
Contactors and Starters IEC
Environment:
North American Products
Resolution:
Please see the table below for these values (within approximately + or - 10%)
| Voltage Code | Resistance (Ohms) | Inductance | DC Coil Voltage |
| AD | 4.41 | 0.18 | 5 |
| AL | 9.51 | 0.37 | 5 |
| BD | 101.9 | 3.9 | 24 |
| BL | 213.7 | 8.2 | 24 |
| CD | 207.7 | 8.1 | 36 |
| CL | 494.8 | 19 | 36 |
| DD | 1527 | 55 | 96 |
| DL | 3255 | 122 | 96 |
| ED | 392.7 | 15 | 48 |
| EL | 843.6 | 33 | 48 |
| FD | 2085 | 78 | 110 |
| FL | 4584 | 163 | 110 |
| GD | 2539 | 94 | 125 |
| JD | 26 | 1 | 12 |
| JL | 53.4 | 2.1 | 12 |
| KD | 1661 | 62 | 100 |
| LD | 6262 | 207 | 200 |
| MD | 7472 | 268 | 220 |
| ML | 17824 | 604 | 220 |
| ND | 633.3 | 24 | 60 |
| PD | 3923 | 143 | 155 |
| QD | 4845 | 177 | 174 |
| RD | 29692 | 923 | 440 |
| SCD | 50973 | 1653 | 575 |
| SD | 819.9 | 31 | 72 |
| SL | 1953 | 71 | 72 |
| TD | 14986 | 526 | 305 |
| UD | 9580 | 345 | 250 |
| UL | 22158 | 745 | 250 |
| VD | 18944 | 659 | 348 |
| XD | 59146 | 2053 | 600 |
| ZD | 66.4 | 2.6 | 20 |
| ZL | 147.6 | 5.5 | 20 |
Released for: Schneider Electric Canada