What is the resistance or ohms value for the TeSys DC Coils on an LC1D09 thru LC1D38?
Issue:
Need to know resistance or ohms value for the TeSys DC Coils on an LC1D09 thru LC1D38

Product Line:
Contactors and Starters IEC

Environment:
North American Products

Resolution:


Please see the table below for these values (within approximately + or - 10%)
Voltage CodeResistance (Ohms)InductanceDC Coil Voltage
AD 4.410.185
AL 9.510.375
BD 101.93.924
BL 213.78.224
CD207.78.136
CL494.81936
DD15275596
DL 325512296
ED392.71548
EL843.63348
FD 208578110
FL4584163110
GD 253994125
JD 26112
JL53.42.112
KD 166162100
LD6262207200
MD 7472268220
ML 17824604220
ND633.32460
PD 3923143155
QD4845177174
RD 29692923440
SCD 509731653575
SD819.93172
SL 19537172
TD14986526305
UD 9580345250
UL 22158745250
VD 18944659348
XD 591462053600
ZD66.42.620
ZL147.65.520