Can (3) separate mount single pole overload relays be used together for a 3phase load?
Issue:
9065HA overload

Product Line:
NEMA style Overload Relays

Environment:
Thermal Overload Relays

Resolution:
Yes. Wire the (3)NC contacts in series so that the control circuit is interrupted when any pole trips.
This applies to the 9065 melting alloy and bimetallic types.