What is the Short Circuit Current rating (SCCR) for the 8536 starters?
Issue:
Short Circuit Current rating (SCCR) for the 8536 starters

Product Line:
Nema and Definite Purpose and Starters

Environment:
North American Products

Cause:
Needs the short current circuit rating (SCCR) for the 8536 starters.

Resolution:
The following interrupting ratings have been established by UL and will apply to the starter only. Horsepower ratings are 480v 3phase.
Horsepower SCCR(A)
>1 thru 505,000
51 thru 200 10,000
201 thru 40018,000
401 thru 60030,000