Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Can a QO2200 (or QO2150 or QO2175) be used in an NQ panelboard?

Issue:
QO2200 (or QO2150 or QO2175) and NQ Panelboards

Product Line:
QO circuit breakers sold and supported in the USA.

Environment:
Application/installation

Cause:
Requirement for a 200A/2P (or 150A/2P or 175A/2P) branch breaker in an NQ panelboard.

Resolution:
Yes QO2200(VH), QO2150(VH) or QO2175(VH) breakers can be used in single phase, NEMA 1, 400A and 600A NQ panelboards. Each breaker takes four pole spaces. Installation into three (3) phase interiors is not allowed as it may create a phase to phase short circuit.

  • Only maximum of four (4) 150, 175 and 200A breakers can be installed in NEMA 1 enclosures. It will also require three-point latch trim fronts (NCxxV( )3P).

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings