Can a QO2200 (or QO2150 or QO2175) be used in an NQ panelboard?
Issue:
QO2200 (or QO2150 or QO2175) and NQ Panelboards

Product Line:
QO circuit breakers sold and supported in the USA.

Environment:
Application/installation

Cause:
Requirement for a 200A/2P (or 150A/2P or 175A/2P) branch breaker in an NQ panelboard.

Resolution:
No, this breaker is not UL listed or warranted for application in an NQ panelboard.
THIS BREAKER IS FOR USE IN SINGLE PHASE QO LOAD CENTERS ONLY.