What type secondary fuses are used in MCC starter units with control transformers? <br />What is the part number?
Issue:
Fusing for MCC buckets

Product Line:
Motor Control Centers

Environment:
Applies to MCC buckets by SquareD/Schneider Electric

Cause:
OverCurrent Protection for Control Transformers

Resolution:

Secondary fuses are FRN-R type fuses
120V 50VA CPT- .5 amp 25413-00060
120V 100VA CPT- 1.0 amp 25413-00090
120V 150VA CPT- 1.6 amp 25413-00130
120V 300VA CPT- 3.2 amp 25413-00190
120V 500VA CPT- 5.0 amp 25413-00230


Schneider Electric Canada

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

  • Product Selector

    Quickly and easily find the right products and accessories for your applications.

  • Get a Quote

    Start your sales inquiry online and en expert will connect with you.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Help Center

    Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings