Can the ELM type ground fault modules be used on a 4 wire system?
Issue:
Can the ELM type ground fault modules be used on a 4 wire system?
Product Line:
Ground fault protection
Resolution:
The ELM150HD and ELM250JD earth leakage module are designed for 3 wire applications only. A neutral CT is not available and they cannot be used on 4 wire applications.
Can the ELM type ground fault modules be used on a 4 wire system?
Product Line:
Ground fault protection
Resolution:
The ELM150HD and ELM250JD earth leakage module are designed for 3 wire applications only. A neutral CT is not available and they cannot be used on 4 wire applications.