Can the PowerPact H and J breakers be used on a corner grounded delta system?
Issue:
Can PowerPact H and J breakers be used on a grounded B phase system?

Product Line:
Circuit Breakers

Resolution:
Yes, the PowerPact H and J breakers can be used on 3 phase, 3 wire grounded B phase systems.
  • A 2p breaker with the special 1Ø-3Ø marking may be used on a 240 Vac or 480 Vac corner grounded system (see specific breaker label for its particular interrupt rating)
  • A 3p breaker may be used on a 240 Vac or 480 Vac corner grounded system without special marking
See the attached file.

Schneider Electric Canada

Attachment(s)
corner gounded.xlsx [98.38 KB]
Corner-Grounded Delta 2700DB0202.pdf [124.08 KB]