Issue:
Can a 200A subfeed breaker be installed into a 400A NF panelboard?
Product Line:
NF Panelboard
Environment:
Application
Cause:
Add in the Field
Resolution:
A NF600SFBJ Sub feed Breaker kit would allow a J*L36200 circuit breaker to be sub fed out of the Panel, opposite end of the Mains.
Note: Back box size must be increased, refer to the NF panelboard section of the current Digest for box selection, see copy of Digest 178, pages 9-36 and 9-37, Tables 9.79 and 9.80 below:

Can a 200A subfeed breaker be installed into a 400A NF panelboard?
Product Line:
NF Panelboard
Environment:
Application
Cause:
Add in the Field
Resolution:
A NF600SFBJ Sub feed Breaker kit would allow a J*L36200 circuit breaker to be sub fed out of the Panel, opposite end of the Mains.
Note: Back box size must be increased, refer to the NF panelboard section of the current Digest for box selection, see copy of Digest 178, pages 9-36 and 9-37, Tables 9.79 and 9.80 below: