Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is the maximum distance for 225A Powerbus busway run?

Issue:
Powerbus max distance

Product Line:
Powerbus 225 Busway

Environment:
Products sold in North America

Cause:
Voltage drop

Resolution:
There is no maximum distance restrictions using the 225 amp Powerbus busway.
Note:  Powerbus does have a 2.5Volt drop per every 100 feet.This is based on 100% power factor (Pf).

Schneider Electric Canada

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings